Skip to content

Cable voltage drop calculator

On a long line, some voltage is lost to the conductor's resistance — the load ends up with less than the source. The calculator estimates the loss from material, cross-section, length, and current.

The line from panel to load, with the drop shown against the limit Panel Load Drop relative to the limit 0 10 %

Input data

Result

Voltage drop, ΔU %

Fill in the fields — the verdict will appear here

Voltage drop, ΔU В

The limit for power and lighting circuits is usually no more than 5%. Reactive resistance of the conductor is ignored (acceptable for cross-sections up to roughly 50–95 mm²).

How it's calculated

  1. Conductor resistance is calculated from its length and cross-section: the longer the line and the thinner the conductor, the bigger the loss.
  2. The multiplier depends on the network: in single-phase, current travels there and back, so the length doubles; in three-phase, √3 replaces the 2.
  3. The loss is compared to the supply voltage and converted to a percentage — the limit for power and lighting circuits is usually no more than 5%.

Example: Copper, three-phase, 50 m, 20 A current, 4 mm² cross-section at 380 V → a drop of 7.58 V, which is 1.99% — comfortably within limits.

ΔU = k·ρ·L·I / S, where k = 2 (single-phase) or √3 (three-phase); ρ — resistivity (copper 0.0175; aluminum 0.0294 Ω·mm²/m).

This is an estimate

Verify final values against current standards, the project design, and equipment nameplates.

All calculators